6- When any of the thermocouple (TC) faults are detected,
output power will be cut-off automatically and the
temperature display will be blanked out. The leftmost
digit will show “ ” for (TC open), “ ” for (TC reverse)
or “ ”for No Heat and flash twice per second.
B.Automatic Operation with CompuStep
®
system
When starting from cold, it is recommended that the
CompuStep system be used, as this will serve to lengthen
heater life considerably.
1- Position the mode select switch to CompuStep mode
(“ ”).
2- Set the desired temperature on the setpoint switch.
3- Turn on the AC power.
4- After reset delay, the measured temperature will be
displayed. If temperature is less than 200 degrees F
(93°C) the controller will enter the CompuStep mode.
This is indicated by the step symbol “ ” on the leftmost
digit. During this mode, the controller gradually
increases power to load in small steps and limits the
load temperature to 256 degrees F (124°C). After 5
minutes, the controller will exit from CompuStep mode
and automatically go to setpoint. Any thermocouple
faults detected during the 5 minute interval will cause
the CompuStep mode to end prematurely. A standby
command from a SAM module will also terminate
CompuStep mode. When CompuStep ends, the
controller will operate as described in the Automatic
Closed-Loop Operation section. If temperature is above
200 degrees F (93°C), controller will bypass CompuStep
and go directly to setpoint.