C. Manual Open-Loop Operation
1- Position the mode select switch to open-loop (“ ”).
2- Turn the AC power on.
3- After reset delay, the controller will display the percent-
age of output power as adjusted by the power control
knob. The percentage power indicator will be on. Thus
0.00 corresponds to 0% (no power) and 1.00
corresponds to 100% (full power). The leftmost digit will
display open-loop mode ( “ ” ). 75% power is shown
as 0.75.
D. Manual Control Pre-Set
The following procedure can be used to pre-set the Manual power
control knob position in the event of a thermocouple break in
closed-loop operation.
A good thermocouple is required to start with, as this procedure
compares the temperature attained using automatic (closed-loop)
control with that obtained using manual (open-loop) control.
When the temperature is the same using either automatic or
manual control, then the position of the Manual power control
knob is correct.